On 15 October 2026 the previous version of the IET Wiring Regulations is withdrawn. From that date BS 7671 Amendment 4 is the only current edition of the UK standard for electrical installations, and anything designed, installed, altered or inspected is measured against it.
Amendment 4 was published in April and contractors have been able to work to it since then, so for many of them the date is a formality. For building owners, estates teams and facilities managers it is worth a closer look, because this amendment reaches into things that were never thought of as electrical work. The most obvious is the data cabling that now powers your cameras, wireless access points and phones.
What BS 7671 Amendment 4 is
BS 7671 is not law in itself, but it is the recognised standard used to show that an electrical installation meets the Electricity at Work Regulations 1989 and Building Regulations. Amendment 4, formally BS 7671:2018+A4:2026, rolls the 2018 edition and every amendment since into a single consolidated book, replacing the brown book most electricians have worked from since 2022.
The IET gave the industry six months to move across. That window closes on 15 October, when the Amendment 3 version is withdrawn.
Power over Ethernet is now part of the wiring regulations
This is the change most likely to affect a modern commercial building. Amendment 4 introduces a dedicated section on Power over Ethernet, bringing PoE inside the scope of BS 7671 for the first time.
The reason is simple. A decade ago a data cable carried data and not much else. Today the same cable powers CCTV cameras, access points, desk phones, access control readers and increasingly lighting and building sensors. The higher power classes mean a bundle of data cables can carry a meaningful amount of current, and current produces heat. Heat in a tightly packed bundle affects both safety and performance, which is exactly the problem we described in why your cameras keep dropping out.
In practical terms, PoE now needs to be treated as a power circuit as well as a data link. Cable selection, bundle sizes, containment, derating and the load on each switch all need to be considered at design stage rather than discovered after handover.
Functional earthing for ICT equipment
Amendment 4 also adds requirements for functional earthing and functional equipotential bonding of information and communication technology equipment and systems. That covers comms rooms, data cabinets and screened cabling systems, where earthing is about the equipment working reliably as well as about protection against electric shock.
It is another area where the electrical and data sides of a project have to be designed together. A cabinet can be perfectly installed from a data point of view and still fall short if nobody has considered how it is earthed.
EICRs will read differently
From 15 October, Electrical Installation Condition Reports are carried out to Amendment 4 using the revised model forms, so your next report may not look like your last one.
The most significant change is to the observation codes. As NICEIC explains in its Amendment 4 guidance, an FI code (further investigation) no longer makes an installation unsatisfactory on its own, and C3 and FI observations are now listed separately from C1 and C2 on the report. The wording of FI has also softened, from investigation required without delay to investigation advised.
This cuts both ways. A report that would once have come back unsatisfactory because of an FI code may now come back satisfactory, with observations. It is worth reading the observations rather than only the outcome, because an FI still means somebody has seen something worth looking into.
Other changes worth knowing about
A new chapter covers stationary secondary batteries used for energy storage. If your site is adding solar with battery storage, or battery backup for critical systems, the installation now has specific requirements covering protection, isolation, ventilation and fire safety.
The section covering medical locations has also been significantly revised, which matters to anyone responsible for healthcare premises.
Does my existing installation now fail?
No. Amendments to BS 7671 are not retrospective. An installation that met the edition in force when it was installed is not unsafe simply because the standard has moved on. However, new work, alterations and additions will all be assessed against BS 7671 Amendment 4, and so will your next periodic inspection.
Three things to do before 15 October
Check when your next EICR is due, and confirm that it will be carried out and issued to Amendment 4.
If you have PoE work planned, such as a CCTV upgrade, a wireless refresh or new access control, ask how the design accounts for power and heat as well as data. The answer should cover cable type, bundle sizes and the load on each switch.
If you are adding battery storage or working in medical locations, confirm that the designer is working to the new requirements rather than to the book they have always used.
Why electrical and data now belong in the same conversation
BS 7671 Amendment 4 formalises something we have seen on site for years. The line between electrical work and data work has disappeared in most buildings, and problems tend to appear where one trade hands over to another.
Multiconnect is NAPIT approved and delivers electrical installation and structured data cabling through one accountable team. Every installation is tested and certified before we leave site. If you would like to talk through how Amendment 4 affects a project you have planned, get in touch.